Calculate panel dimensions from Single Line Diagram (SLD)
Switchgear size, form factor, installation type, cable termination position
Indoor/Outdoor, Front/Back cable termination, Single/Double door
Width, Height, Depth based on IEC/NEC standards
| Switchgear Type | Rating (A) | Width (mm) | Height (mm) | Depth (mm) |
|---|---|---|---|---|
| MCB | ≤ 63 | 300 | 275 | 300 |
| MCCB | 63-100 | 350 | 300 | 300 |
| MCCB | 125-250 | 350-400 | 300-350 | 300-350 |
| MCCB | 400-630 | 600 | 400 | 350-400 |
| MCCB | 800 | 600 | 600 | 700 |
| MCCB | 1250-3200 | 800 | 850 | 1000 |
| ACB Rating | Width (mm) | Height (mm) | Depth (mm) |
|---|---|---|---|
| 800A | 700 | 800 | 800 |
| 1600A | 800 | 800 | 850 |
| ≤ 3200A | 800 | 850 | 1000 |
| > 3200A | 1400 | 1000 | 1200 |
| Component | Position | Width/Height (mm) | Depth (mm) |
|---|---|---|---|
| Busbar | Horizontal | 300-400 | 300 |
| Busbar | Vertical | 300-400 | 300 |
| Cable Alley | Vertical | 300-350 | 300 |
Formula: Total Width = Incoming Width + Busbar Width + Max(Outgoing Widths) + Cable Alley Width
Where:
Formula: Total Height = Base(75mm) + Σ(Switchgear Heights) ≤ 2200mm
Constraints:
Formula: Total Depth = Max(Incoming Depth, Outgoing Depth) + Cable Termination Offset
Where:
Given: Incoming: 1250A ACB, Outgoing: 2×630A MCCB, 3×400A MCCB
Calculations: